I have a question about this section:

300.11 Securing and Supporting.
(B) Wiring Systems Installed Above Suspended Ceilings.
Cables and raceways shall not be supported by ceiling grids.

I worked a job where they installed a second ceiling grid system strictly for mounting electrical conduit and devices. There were no tiles installed in it. It was installed two or three feet above the actual ceiling. It was the exact same grid normally used for suspended ceilings.

Legal or not?

LarryFine

Master Electrician Electric Contractor Richmond VA
Location
Henrico County, VA
Occupation
Electrical Contractor
  • Mar 23, 2018
  • #2

Is it possible the upper grid was the original one, and the lower one the new one?

Either way, I'd say the upper grid is not "the ceiling grid" and thus okay for support.

Coppersmith

Senior Member
Location
Tampa, FL, USA
Occupation
Electrical Contractor
  • Mar 23, 2018
  • #3

LarryFine said:

Is it possible the upper grid was the original one, and the lower one the new one?

Actually, new construction.

LarryFine

Master Electrician Electric Contractor Richmond VA
Location
Henrico County, VA
Occupation
Electrical Contractor
  • Mar 23, 2018
  • #4

Answer still the same: there's only one ceiling, thus one ceiling grid.

The grids are separately supported, right?

J

JFletcher

Senior Member
Location
Williamsburg, VA
  • Mar 23, 2018
  • #5

In the strictest interpretation of that part of 300.11, that installation is not compliant - it doesn't say the ceiling grid, it says ceiling grids.

Two sentences before that though it says, and I quote:

" support wires and associated fittings that provide secure support and that are installed in addition to the ceiling grid support wires shall be permitted as the sole support"

Which in my humble opinion and code interpretation makes it legal IF the two ceiling grids had two completely separate sets of support wires.

J

JFletcher

Senior Member
Location
Williamsburg, VA
  • Mar 23, 2018
  • #6

I think the call could go either way. You have a secondary, auxiliary, or unused ceiling grid above a ceiling grid, but it is still a ceiling grid. If everything up there would stay in place if you remove the grid and just had the tie wires holding it in place, there would be no question whatsoever that it is code compliant.

I've only seen one building with a basic double grid system, and none of the electrical was supported by the original grid. The second, lower grid was added years later.

I would absolutely hate to rip all of that out because of a simple "the" missing from 300.11.

electrofelon

Senior Member
Location
Cherry Valley NY, Seattle, WA
  • Mar 24, 2018
  • #7

Doesn't the exception to 300.11 (potentially) come into play here?

infinity

Moderator

Staff member

Location
New Jersey
Occupation
Journeyman Electrician
  • Mar 24, 2018
  • #8

If the upper grid were installed solely for the support of the conduit then IMO it's up to the AHJ to decide if its strength is adequate to be used as means of support.

Coppersmith

Senior Member
Location
Tampa, FL, USA
Occupation
Electrical Contractor
  • Mar 24, 2018
  • #9

I did this job about 10 years ago and the reason I'm asking about it now is that I'm doing a "changes from NEC 2014" training, I read this section, and it caused me to think about that job.

If I am remembering correctly, the upper grid was separately supported from the lower, but it was not tied to the lower. It was attached to the walls as per normal. I should also note that we were laying conduit directly on top of the grid members.

After reading the responses so far, I'm tending to think this was not a ceiling grid. It was an independent conduit support system that just happened to be constructed out of ceiling grid material.

G

GoldDigger

Moderator

Staff member

Location
Placerville, CA, USA
Occupation
Retired PV System Designer
  • Mar 24, 2018
  • #10

Coppersmith said:

I did this job about 10 years ago and the reason I'm asking about it now is that I'm doing a "changes from NEC 2014" training, I read this section, and it caused me to think about that job.

If I am remembering correctly, the upper grid was separately supported from the lower, but it was not tied to the lower. It was attached to the walls as per normal. I should also note that we were laying conduit directly on top of the grid members.

After reading the responses so far, I'm tending to think this was not a ceiling grid. It was an independent conduit support system that just happened to be constructed out of ceiling grid material.

It may well be an independent support system, but IMHO supporting conduit or wires on the grid members rather than directly from the support wires is still a bad idea and a violation.

Sent from my XT1585 using Tapatalk

J

JFletcher

Senior Member
Location
Williamsburg, VA
  • Mar 25, 2018
  • #11

GoldDigger said:

It may well be an independent support system, but IMHO supporting conduit or wires on the grid members rather than directly from the support wires is still a bad idea and a violation.

Sent from my XT1585 using Tapatalk

I agree. Ceiling grids are to support ceilings. It may be adequate to support coppersmith installation, however had he tried to use that grid to support multiple runs of say 2in IMC, it probably would have buckled those thin aluminum t bars and the whole thing would have come down if those conduits were not supported
directly by the support wires.

Some ceiling grids are strong enough to support fixtures, like a heavy-duty grid-like is in a commercial kitchen. Those drop tiles are heavier than sheetrock of an equal size. And lightweight devices, like smoke detectors, I believe can be supported by the grid, perhaps even the tile itself.

If I were the inspector on that job, I would have failed it, however I would not have made him remove the grid rather just install wires to the ceiling to support all of the conduits. At that point the grid is irrelevant and it's not supporting anything.

Eta: one of the first jobs I ever cable with v/d/v cable was a 44 room addition to a hotel that was up sizing and changing brands. Right before the rough-in inspection, my boss came by to see how everything was going. all of my cables, save for one we're all nicely and neatly bundled and supported, however this one cable had a bit of slack in it between 2 D-rings and was touching the grid. There was probably less than a gram of weight on that ceiling, however he made me pull it tight so that it was not touching the Grid at all. In that case though, one of the concerns is a firefighter poking an axe through the ceiling and getting it hung up in a wad of cable and bringing it all down on himself

Last edited:

Status
Not open for further replies.
  • Home
  • Forums
  • Active Forums
  • NEC
ceiling grid conduit mounting (2024)
Top Articles
Small Party Hall Near Me
Nearest Quiktrip From My Location
Woodward Avenue (M-1) - Automotive Heritage Trail - National Scenic Byway Foundation
Cranes For Sale in United States| IronPlanet
Promotional Code For Spades Royale
No Limit Telegram Channel
Kokichi's Day At The Zoo
Pga Scores Cbs
Paris 2024: Kellie Harrington has 'no more mountains' as double Olympic champion retires
Eric Rohan Justin Obituary
Videos De Mexicanas Calientes
Free VIN Decoder Online | Decode any VIN
Green Bay Press Gazette Obituary
Skylar Vox Bra Size
Wordscape 5832
Kitty Piggy Ssbbw
New Stores Coming To Canton Ohio 2022
Best Uf Sororities
How do I get into solitude sewers Restoring Order? - Gamers Wiki
Urban Airship Expands its Mobile Platform to Transform Customer Communications
Craigslist Pinellas County Rentals
Water Trends Inferno Pool Cleaner
Amih Stocktwits
Mychart Anmed Health Login
Qual o significado log out?
11 Ways to Sell a Car on Craigslist - wikiHow
Jobs Hiring Near Me Part Time For 15 Year Olds
Regal Amc Near Me
Low Tide In Twilight Ch 52
Kirk Franklin Mother Debra Jones Age
Joann Fabrics Lexington Sc
The Posturepedic Difference | Sealy New Zealand
Greater Orangeburg
Kids and Adult Dinosaur Costume
L'alternativa - co*cktail Bar On The Pier
Yoshidakins
Garrison Blacksmith's Bench
Craigslist Lakeside Az
Wal-Mart 2516 Directory
Craigslist Ludington Michigan
Craigslist Putnam Valley Ny
The Holdovers Showtimes Near Regal Huebner Oaks
15 Best Things to Do in Roseville (CA) - The Crazy Tourist
PruittHealth hiring Certified Nursing Assistant - Third Shift in Augusta, GA | LinkedIn
Fwpd Activity Log
Walmart Pharmacy Hours: What Time Does The Pharmacy Open and Close?
Nid Lcms
SF bay area cars & trucks "chevrolet 50" - craigslist
Shipping Container Storage Containers 40'HCs - general for sale - by dealer - craigslist
Willkommen an der Uni Würzburg | WueStart
Www Extramovies Com
Primary Care in Nashville & Southern KY | Tristar Medical Group
Latest Posts
Article information

Author: Edmund Hettinger DC

Last Updated:

Views: 5326

Rating: 4.8 / 5 (58 voted)

Reviews: 89% of readers found this page helpful

Author information

Name: Edmund Hettinger DC

Birthday: 1994-08-17

Address: 2033 Gerhold Pine, Port Jocelyn, VA 12101-5654

Phone: +8524399971620

Job: Central Manufacturing Supervisor

Hobby: Jogging, Metalworking, Tai chi, Shopping, Puzzles, Rock climbing, Crocheting

Introduction: My name is Edmund Hettinger DC, I am a adventurous, colorful, gifted, determined, precious, open, colorful person who loves writing and wants to share my knowledge and understanding with you.